BASICS OF REFRIGERATION AND AIR CONDITIONING
Er
.Deepak Sathe
DEE
SDE(E)
BSNL,Mumbai
2006
2006
BASICS OF REFRIGERATION :-
The
word ‘refrigerate’ means to chill or freeze a substance i.e. to lower its
temperature by removing heat.
Refrigeration
is the process of removing heat from a substance and rejecting the heat so
removed to the atmosphere which is at a higher temperature level.
Heat
always flows from a body at a high temperature to another at a lower
temperature. Hence when we want heat flow in reverse direction i.e. from lower
to higher temperature level or in other words when we want to lower the
temperature below the surrounding atmospheric temperature it requires external
energy.
Refrigeration
is accomplished by various methods:- 1) Vapour compression system 2) Vapour absorption system etc…..
Mechanical
vapour compression system is practical application of Charles’s law Pressure
varies proportionate to temperature. The boiling point of a liquid ( or
condensing temperature of a gas) can be varied at will by varying pressure of
vapour in a enclosed space above the liquid level (i.e. in saturated condition)
Refrigerants are heat carrying mediums which during
their cycle in the refrigeration system absorb heat at ( Low pressure) a low
temperature level and discard the heat so absorbed at a higher level i.e.
ambient temperature (at High pressure).
These
refrigerants have boiling points much below ordinary room temperature. So they
exist as gases and are held in liquid state by keeping them under pressure such
as in refrigerant cylinder.
From pressure-temperature chart (at saturation) we
get boiling point and their corresponding pressure.
For R 22
|
|
Boiling point ( 0 F)
|
Pressure (PSIG)
|
-41
|
0 (At atmospheric pressure)
|
49.1
|
82.5
|
75
|
132.2
|
120
|
259.9
|
125
|
277.9
|
127.4
|
286.9
|
130
|
296.9
|
1)
Evaporator: - The process of heat
removal from the substance / air to be cooled is done in evaporator. The
refrigerant is in liquid state as it absorbs maximum heat during vaporization.
At the inlet of evaporator, the refrigerant is predominately in the liquid form
with small amount vapour formed as a result of flashing at the expansion valve.
SST is 90 F
to 100 F (49.1 OF) corresponding pressure is 82.5 PSIG
neglecting pressure losses in evaporator.
As refrigerant
passes through the evaporator more and more liquid is vaporized by the load,
when it reaches the end of evaporator it is purely in the super heated vapour
state.
D-X system which we use in package air conditioner,
is a system where the air to be cooled is directly passed over the evaporator
coil inside which refrigerant is boiling.
2)
Compressor:- For closed cycle
of vapour compression system ,the
refrigerant coming out of the evaporator ( superheated low pressure vapour)
must be compressed corresponding to the saturation temperature higher than
ambient air temperature ( in case of air cooled system).
The
compressor acts as pump to circulate refrigerant through closed system.
Types:- a) Open or Hermetically closed.
b) Reciprocating, Screw, Rotary, Centrifugal or
Scroll
Compressor
manufacturers publish rating charts/tables showing capacity for various suction
temperatures and discharge temperatures. Capacity increases with increase of
suction temperature whereas it decreases with increase of discharge
temperature.
Discharge
pressure in absolute units
Suction pressure in absolute units
Pressure
in Absolute units = PSIG + 14.7
Refrigeration
effect produced BTU /
hour
Power
consumed
Watt
EER is maximum in
case of Scroll type compressor.
3)
Condenser:- The function of
condenser are
1) To desuperheat high pressure gas.
2) To condense it
from gas to liquid.
3) To Sub cool
liquid.
SDT is 530
C (127.4 0F) corresponding pressure is 286.9 PSIG neglecting pressure
losses in condenser.
Depending upon type
of cooling medium condensers are 1) Air cooled 2) Water cooled 3) Evaporative
(combination of both air & water).
In air cooled
condenser refrigerant is cooled by ambient air, the ambient air temperature is
more than the temperature of water. Hence the condensing temperature is higher
in case of air cooled condenser than water cooled condenser. Heat transfer
efficiency increases when the medium is liquid. This makes water cooled system
more efficient than air cooled but the scarcity of water compels to use air
cooled system.
4)
Throttling device:- (Thermostatic
expansion valve) The pressure of the liquid refrigerant coming out of condenser / receiver has to be reduced so that it can vaporize at desired temperature in the
evaporator (SST).
Sufficient
refrigerant has to be fed into the evaporator to meet load. Externally
equalized thermostatic expansion valve is normally used, feeler bulb is placed
on suction line.
Superheating:-If the temperature of the refrigerant gas is more
than its saturation temperature ,the gas is said to be in superheated condition.
TEV
is adjusted for superheat of 100F means the suction line where
feeler bulb is mounted there is no liquid but vapour in superheated state by 100F
above its saturation temperature.
Superheat provided is the difference between the
temperature of the suction line ( place where feeler bulb is mounted) and the
saturated temperature corresponding to the evaporator pressure( i.e. suction
pressure neglecting pressure drop in evaporator or add 20F for
suction pressure drop).
As
the superheat increases compressor capacity drops due to reduction in density
of gas, HP per ton increases. But this superheat is required to safe guard
compressor against liquid flood back.
Sub cooling:- If the temperature of the refrigerant gas is less
than its saturation temperature ,the liquid is said to be in sub-cooled condition.
The
high pressure ,high temperature liquid coming out of condenser must be cooled
down and reduce its pressure before entering evaporator, this is achieved by
throttling device. The cooling occurs automatically when liquid passes through
TEV.A portion of liquid refrigerant boils taking latent heat of vaporization
from liquid itself.
For
thermodynamics tables of R22
Temp.
(0F)
|
Enthalpy
of liquid
(BTU/lb)
|
Enthalpy
of vapour
(BTU/lb)
|
Latent
heat of vaporization(BTU/lb)= Enthalpy diff between vapour & liquid
|
119
|
42.45
|
112.5
|
70.05
|
40
|
21.42
|
108.14
|
86.72
|
The
amount of heat to be removed to cool liquid from 1100 F TO 400
F = 42.45 – 21.42 = 21.03
latent heat of vaporization at 400F
= 86.72
i.e.
24.2% of latent heat of vaporization is utilized to cool liquid refrigerant to
evaporator temperature level.
The
refrigeration is accomplished mainly by absorption of its latent heat of
vaporization by boiling liquid refrigerant in the evaporator.
The
24.2% of latent heat of vaporization is
used in cooling down liquid while passing through TEV ,balance 75.8% gives
effective refrigeration effect ,known as Net Refrigeration Effect (NRE).
Thus
NRE decreases as the difference between condensing and evaporating temperature
widens.
Also
with sub cooling ,as the temperature from which liquid is to be cooled is
reduced, the NRE increases and mass flow rate per ton reduces.
Manufacturers
rating chart gives capacity / power for
wide range of SST & SDT at liquid sub cooled at 150F.
For
every degree increase above 150F of liquid sub cooling, there is
increase in compressor capacity by 0.5%.without any change in power
requirement, thus increases efficiency.
Over
sizing air cooled condenser ( or by use
of liquid –suction heat exchanger ) so as to take care of de-superheating,
condensing and liquid sub cooling, we can increase efficiency of Refrigeration
system.
Small
amount of vapour present in liquid line
occupy substantial volume ,which offer high resistance to flow in liquid line. This
effects capacity of refrigerant system. Vapour can be present in the liquid
line 1) If condensation is not complete. 2) Shortage of refrigerant. 3) Excessive
pressure drop in liquid line causing formation of flash gas.
Pressure Drop – Liquid lift:- When liquid / gas flows through pipe ,resistance
is offered by pipe walls, results in pressure drop .In refrigeration ,pressure
drops are expressed in temperature units. If liquid is in saturated condition
(not sub cooled) even small pressure drop can cause liquid flashing resulting
in formation of flash gas. Similarly where an evaporator is located at higher
level than the condenser, the pressure drop due to liquid lift (lift against
gravity) is very high causing heavy liquid flash.
R22
|
|
Kg/cm2
per mtr
|
0.035
|
Psi
per ft
|
0.5
|
Selection of Design criteria:-
1)
Saturated suction temperature (SST):-
Compressor capacity varies directly with SST. Higher SST better will be the capacity.
Hermetic
/ Semi hermetic compressor - 100C or 500F
Open
type compressor- 150C or
590F
This
is governed by 1) for ensuring suction gas cooling of motor windings.
2)
Saturated discharge temperature (SDT):-
Compressor capacity varies inversely
with SDT.
Depend
upon i) type of condenser air cooled or water cooled.
ii) Highest outside condition.
( ETD) Entering Temperature diff = (SDT –
entering temp of condenser i.e.max ambient temp)
Normally taken as 100C to 170 C ( 200F to 300F)
3)
Sub cooling:- Minimum 150F ( sub cooling can save
energy up 10%)
4)
Super heat:- Minimum 60C ( for safety of compressor)
5)
Static pressure:- 35 mm WG.( for
high sensible units it is better to take 25 mm WG as cfm for is more than the units for comfort
cooling and installing units in area to be air-conditioned, as power
consumption of continuous operated blower is @ 25% )
No comments:
Post a Comment