1) Twin Compressor with single/Twin Ckt. ( for more reliability)
- Capacity of air conditioning plant is worked out based on peak outside
conditions prevailing in that area, heat load, lighting load ,occupation
in room ,heat gain from surroundings.
- It is worthwhile to note that both the operating
conditions and the capacity of a refrigerating system change as the load
on the system changes and also depending upon heat gain from surroundings.
- Equilibrium maintained between vaporizing and
condensing sections depending upon internal load and heat gain from
surroundings affects rated capacity at designed operating conditions of
air conditioner.
- When the load on the system is light, the space
temperature will be lower than the average design space temperature, the
evaporator (Δt) will be less than the design (Δt) and the suction
temperature will be lower than the design suction temperature. Therefore,
the system operating conditions will be somewhat lower than the average
design operating conditions and the system capacity will be somewhat less
than the average design capacity.
- Good practice requires that the system be
designed to have a capacity equal to or slightly in excess of the average
maximum sustained load. This is done so that the system will have
sufficient capacity to maintain the temperature and humidity at the
desired level during periods of peak loading. Obviously, as the cooling
load decreases, there is a tendency for the system to become oversized in
relation to the load.
- The degree of variation in the length of the on
and of cycles well depend on the degree of load fluctuation.
- The design conditions occur may
be, for example, during only 1% of the total time the equipment is in
operation throughout the year.
·
Multiple-System
Capacity Control is one of the methods of controlling capacity.
- With Double independent
refrigerant circuit, capacity control of 50% and 100% is possible with blower
fan common for total capacity , is essential as our load is predominately sensible
load.
- It is desirable to use of Double independent
refrigerant circuit where the refrigeration load is variable. ( Less
capital cost and easy maintenance and more reliability )
- For Heat load 10
TR to 20 TR -- 7 TR
with n+1 Configuration
- More than 20 TR -- 14 TR with n+1 configuration. For n >6 n+2 configuration
- For heat load calculation fresh air requirement,
duct heat & return air heat gain not to be considered. ( Fresh air
arrangement not required, infiltration of air during opening of door is
sufficient to make up oxygen as it unnecessarily increase latent load .) (Shortest
air circulation path / route., Arrange racks in hot aisle / cold aisle,
Matching server air flow by aisle., Reduce mixing and short circuits.,
Provide isolation between hot and cold spaces. And free return air path., Best
option is to install units in area to be conditioned)
2) Electronic Expansion valve.
The conventional TXV is controlled by springs, bellows, and push
rods. The spring force is a closing force on the TXV. The evaporator pressure,
which acts under the thermostatic element's diaphragm, is also a closing force.
An opening force is the remote bulb force, which acts on top of the
thermostatic element's diaphragm.
There
is also a liquid force from the liquid line, which acts on the face of the needle
valve and has a tendency to open the valve. However, this force is cancelled
out when using a balanced port TXV. Working together, these forces maintain a
constant evaporator superheat in a refrigeration system. There are no
electronic devices associated with a conventional TXV.
Sensors
The electronic signals sent by the controller to
the EEV are usually done by a thermistor connected to discharge airflow in the
refrigerated case. A thermistor is nothing but a resistor that changes its
resistance as its temperature changes. Other sensors are often located at the
evaporator inlet and outlet to sense evaporator superheat. This protects the
compressor from any liquid floodback under low superheat conditions. Pressure
transducers can also be wired to the controller for pressure/temperature and
superheat control. Pressure transducers generally have three wires. Two wires
supply power and the third is an output signal. Generally, as system pressure
increases, the voltage sent out by the signal wire will increase. The
controller uses this voltage to calculate the temperature of the refrigerant
with the use of a pressure/temperature table programmed into the controller.
The benefits derived from the
installation of electronic expansion valves are as follows:
•
Improved control of liquid refrigerant flow to evaporator. The evaporator is
always optimally filled with refrigerant. Even with large load variations,
which means an extremely wide range of partial-load operating conditions,
exactly the right amount of refrigerant can be injected.
•
Improved heat transfer, since more evaporator surface area used for boiling
liquid ,less superheat.
•
Raised evaporating temperature and higher suction pressure, reducing energy use
by 2% to 3% per 1ºC in evaporating temperature.
• Reduced
risk of liquid carry-over to compressor, reducing risk of compressor
damage.
• Avoids
need for constant pressure drop across expansion valve.
•
Allows condensing temperature (discharge/head pressure) to reduce at times of
low ambient temperatures
Thereby making air conditioning unit energy
efficient. Hence it is recommended to use Electronic expansion valves.
3) Direct driven fan motor assembly for evaporator.
Backward curved freewheel fans Direct
driven by electronically communicated motors are recommended as they save upto
30% as compared to forward curved centrifugal fans having dampers for cfm
control.
Backward curved centrifugal fans
characteristics are Energy efficient as no transmission loss, easy maintenance,
less noise , high static pressure ,high flow ,power reduces as flow increases
beyond point of highest efficiency. Where as forward curved fans are self
loading type power rises continuously ,dip in pressure curve moreover damper
control is not particularly energy efficient method of air flow control.
The Precision air conditioning units
are used in telephone exchange building having their own transformer substation,
having reasonable voltage stability .Requirement of SMPS power unit for may differ
manufacturer to manufacturer depending upon their microprocessor controller to
make specification generic ,SMPS power supply unit may not insisted.
Provision of Precision air
conditioner as replacement to existing package units in existing setup is not
recommended.
Following are additional comments on precision air conditioning
specification:
1) Precision AC Unit designed for COP 2.9.
- The following definitions are taken from ASHRAE Standard
90.1-1999 (2001).
- Coefficient of performance (COP) – cooling: the ratio of the rate of heat
removal to the rate of energy input, in consistent units, for a complete
refrigerating system or some specific portion of that system under designated operating conditions.
- Energy efficiency
ratio (EER):
the ratio of net cooling capacity in Btu/h to the total rate of electric input
in watts under designated operating
conditions.
- Integrated
part-load value (IPLV): a single number figure of merit based on part-load
EER, COP, or kW/ton, expressing part-load efficiency for air-conditioning
and heat pump equipment on the basis of weighted operation at various load
capacities for the equipment.
- As per ASHRAE 90.1-2004 $ 6.4.1 & ECBC 2007
Unitary Air Conditioning Equipment
|
Equipment class
|
Min COP
|
Min IPLV
|
Test Standards
|
|
Air
cooled chiller <530 kw
(<150
tons)
|
2.9
|
3.16
|
API
550/590-1998
|
|
Air
cooled chiller >530 kw
(>150
tons)
|
3.05
|
3.32
|
API
550/590-1998
|
|
Centrifugal
water cooled chillers <530 kw
(<150
tons)
|
5.8
|
6.09
|
API
550/590-1998
|
|
Centrifugal
water cooled chillers >530 kw and < 1050 kw
(>150
tons and <300 tons)
|
5.8
|
6.17
|
API
550/590-1998
|
|
Centrifugal
water cooled chillers >1050 kw
(>300
tons)
|
6.3
|
6.61
|
API
550/590-1998
|
- BSNL specification requires COP
2.9, at designed conditions i.e. SST 9 to 10 0C & SDT 53 0C for ambient temperature
of 43 0C.
- Considering designed condition
and 35 mm static pressure evaporator fan, it is not possible to achieve
required COP.
2) Check for good installation of
Air cooled Condenser.
- Proper operation and giving
rated capacity at designed conditions / peak conditions of PAC is mainly
depend upon efficient working of Air cooled condenser.
- In case of water cooled system,
checking of cooling tower efficiency by web bulb approach was invariably
done during AT.
- However in case of air cooled
system there is no check of
efficiency of air cooled condenser which is solely depend on entering and
leaving dry bulb temperature.
- Seasonal test shall be conducted only in summer
months April to June and October.
Air entering
condenser shall be at ambient temperature.
Or
- During testing ambient
temperature shall be more than 40 0C.
Capacity calculation by Enthalpy method (Evaporator side ),
Condenser capacity and Capacity from
compressor manufacturer capacity chart at working conditions shall give clear
picture about ENERGY EFFICIENT INSTALLATION OF AC UNITS.
3) Electrical console for Package AC
units.
- In coming FP MCB ,insulated
busbar for distribution ,Motor Protection Circuit Breakers (MPCB)
,suitable size contactor and overload relays shall incorporated to avoid
fire hazards , as these units are preferably installed in area to be
conditioned.
- Provision of wet floor sensor
to indicate water leakage problem.
- Provision of Electrical control
panel at entrance air lock lobby with two incomings electrically &
mechanically interlocked through shunt trip coil and AC cutoff in case of
Fire.
4) Insulation of refrigerant piping / drain pipe inside the conditioned space.
5) Provision of false floor height 600 mm ,avoid refrigerant / drain piping in path of supply air.
5) Use of site suitable package unit
variants.
Different models suitable for site requirement to be
selected as follows
v
Low static
pressure (Installation inside switch room is preferred). / High static pressure
( Ducted units)
v
Condenser
suitable for 350C & 430C ambient temperature ( shall
reduce initial cost ).
v
Upward and
downward flow.
v
Condenser top
and side throw.
Nice job you are doing sir, please upload all the technical circulars and financial powers
ReplyDelete